YASKAWA VIPA System MICRO M13-CCF0000 Manual page 210

Table of Contents

Advertisement

Configuration with TIA Portal
TIA Portal - Project transfer > Option: Transfer via MPI
1
MPI programming cable
2
Activate the terminating resistor via switch
3
MPI network
Proceeding enabling the
interface
Proceeding transfer via
MPI interface
210
A hardware configuration to enable the MPI interface is not necessary. By installing the
extension module EM M09 the MPI interface is enabled.
1.
Turn off the power supply.
2.
Mount the extension module.
3.
Switch on the power supply.
ð After a short boot time the interface X2 MPI(PB) is ready for MPI communica-
tion with the MPI address 2.
Currently the VIPA programming cables for transfer via MPI are not supported. This is
only possible with the programming cable from Siemens. The cables provide a RS232
res. USB plug for the PC and a bus enabled RS485 plug for the CPU. Due to the RS485
connection you may plug the MPI programming cables directly to an already plugged plug
on the RS485 jack. Every bus participant identifies itself at the bus with an unique
address, in the course of the address 0 is reserved for programming devices.
1.
Establish a connection to your extension module via MPI with an appropriate pro-
gramming cable. Information may be found in the corresponding documentation of
the programming cable.
2.
Start the Siemens TIA Portal with your project.
3.
Select in the Project tree your CPU and choose 'Context menu
è Download to device è Hardware configuration' to transfer the hardware configu-
ration.
4.
To transfer the PLC program choose 'Context menu è Download to device
è Software'. Due to the system you have to transfer hardware configuration and
PLC program separately.
Ä Chapter 2.4 'Mounting' on page 13
HB400 | CPU | M13-CCF0000 | en | 16-47
VIPA System MICRO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents