Basics and mounting
General data
Environmental conditions to EN 61131-2
Horizontal installation lying
Vertical installation
Air humidity
Pollution
Installation altitude max.
Mechanical
Oscillation
Shock
Mounting conditions
Mounting place
Mounting position
EMC
Emitted interference
Noise immunity
zone B
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is
necessary.
32
EN 61131-2
EN 61131-2
EN 60068-2-30
EN 61131-2
-
EN 60068-2-6
EN 60068-2-27
-
-
Standard
EN 61000-6-4
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
0...+60°C
0...+60°C
RH1 (without condensation, rel. humidity 10...95%)
Degree of pollution 2
2000m
1g, 9Hz ... 150Hz
15g, 11ms
In the control cabinet
Horizontal and vertical
Comment
Class A (Industrial area)
Industrial area
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
HF field immunity (casing)
80MHz ... 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
HF conducted
150kHz ... 80MHz, 10V, 80% AM (1kHz)
Burst, degree of severity 3
Surge, degree of severity 3 *
HB400 | CPU | M13-CCF0000 | en | 16-47