Deployment I/O periphery
Digital input > Parametrization
X5
Function
1
-
2
-
3
DI 1.0
4
DI 1.1
5
DI 1.2
6
DI 1.3
7
DI 1.4
8
DI 1.5
9
DI 1.6
10
DI 1.7
*) Max. input frequency 100kHz otherwise 1kHz.

5.4.3 Parametrization

5.4.3.1
Adress assignment
Sub module
Input address
DI24/DO16
136
137
5.4.3.2
Hardware interrupt
Parameter hardware con-
figuration
5.4.3.3
Input delay
Parameter hardware con-
figuration
92
Type
LED
-
-
I
green
I
green
I
green
I
green
I
green
I
green
I
green
I
green
Access
BYTE
BYTE
With the parameter 'Hardware interrupt at ...' you can specify a hardware interrupt for
each input for the corresponding edge. The hardware interrupt is disabled, if nothing is
selected (default setting). A diagnostics interrupt is only supported with Hardware inter-
rupt lost. Select with the arrow keys the input and enable the according hardware inter-
rupts.
Here is valid:
n
Rising edge: Edge 0-1
n
Falling edge: Edge 1-0
n
The input delay can be configured per channel in groups of 4.
n
An input delay of 0.1ms is only possible with "fast" inputs, which have a max. input
frequency of 100kHz
input delay for slow inputs is limited to 0.5ms.
n
Range of values: 0.1ms / 0.5ms / 3ms / 15ms
Description
reserved
reserved
Digital input DI 8
Digital input DI 9 / Counter 3 (A) *
Digital input DI 10 / Counter 3 (B) / Frequency 3 *
Digital input DI 11 / Gate 3 *
Digital input DI 12
Digital input DI 13
Digital input DI 14
Digital input DI 15 / Latch 3 *
Assignment
Digital input I+0.0 ... I+0.7 (X1)
Digital input I+1.0 ... I+1.7 (X5)
Ä Chapter 5.4 'Digital input' on page 90. Within a group, the
HB400 | CPU | M13-CCF0000 | en | 16-47