Deployment I/O periphery
Diagnostic and interrupt > Diagnostic interrupt
Diagnostic record set 1 at
pulse width modulation
138
Byte
Bit 7...0
11
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: ... input I+1.4
n
Bit 1: 0 (fix)
n
Bit 2: ... input I+1.5
n
Bit 3: 0 (fix)
n
Bit 4: ... input I+1.6
n
Bit 5: 0 (fix)
n
Bit 6: ... input I+1.7
Bit 7: 0 (fix)
n
12
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: End of measurement channel 0
(End of integration time)
n
Bit 7 ... 1: 0 (fix)
13
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: End of measurement channel 1
(End of integration time)
n
Bit 7 ... 1: 0 (fix)
14
Diagnostic interrupt due to "process interrupt lost" at...
Bit 0: End of measurement channel 2
n
(End of integration time)
n
Bit 7 ... 1: 0 (fix)
15
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: End of measurement channel 3
(End of integration time)
n
Bit 7 ... 1: 0 (fix)
The record set 1 contains the 4byte of the record set 0 and additionally 12byte module
specific diagnostic data. The diagnostic bytes have the following assignment:
Byte
Bit 7...0
0 ... 3
Content record set 0
4
n
Bit 6 ... 0: Channel type (here 70h)
70h: Digital input
71h: Analog input
72h: Digital output
73h: Analog output
74h: Analog input/output
n
Bit 7: More channel types present
0: no
1: yes
5
Number of diagnostic bits per channel (here 08h)
6
Number of channels of a module (here 08h)
Ä 'Record set 0 Diagnostic