Mechanical Installation

◆ Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in an environmental matching the
specifications below.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the
temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Table 1 Installation Environment
Indoors
-10°C to +40°C (IP20/NEMA Type 1 enclosure)
-10°C to +50°C (IP00 enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m, up to 3000 m with derating
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
(Models CIMR-A 2A0004 to 2A0211 and 4A0002 to 4A0165) or,
2
2.0 m/s
2
(Models CIMR-A 2A0250 to 2A0415 and 4A0208 to 4A0675)
Install the drive vertically to maintain maximum cooling effects.
2 Mechanical Installation
Conditions
2
19