Mapping table
The table below shows registers that the SINAMICS V20 converter supports. "R", "W", and
"R/W" in the "Access" column stand for read, write, and read/write respectively. Registers
with * are available only when the optional I/O Extension Module is connected.
HSW (speed setpoint), HIW (actual speed), STW (control word), and ZSW (status word)
refer to control data. For more information, see parameters r2018 and P2019 in Chapter
"Parameter list (Page 193)".
Register No.
MODBUS
Converter
0
40001
1
40002
2
40003
3
40004
4
40005
5
40006
6
40007
7
40008
8
40009
9
40010
10
40011
11
40012
12
40013
13
40014
14
40015
15
40016
16
40017
17
40018
18
40019
19
40020
20
40021
21
40022
22
40023
23
40024
24
40025
25
40026
26
40027
27
40028
28
40029
29
40030
30
40031
31
40032
32
40033
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Description
Ac-
cess
Watchdog time
R/W
Watchdog action
R/W
Frequency setpoint
R/W
Run enable
R/W
Forward/reverse
R/W
command
Start command
R/W
Fault acknowledgement
R/W
PID setpoint reference
R/W
PID enable
R/W
Current limit
R/W
Acceleration time
R/W
Deceleration time
R/W
(Reserved)
Digital output 1
R/W
Digital output 2
R/W
Reference frequency
R/W
PID upper limit
R/W
PID lower limit
R/W
Proportional gain
R/W
Integral gain
R/W
Differential gain
R/W
Feedback gain
R/W
Low pass
R/W
Frequency output
R
Speed
R
Current filtered
R
Torque
R
Actual power
R
Total kWh
R
DC bus voltage
R
Reference
R
Rated power
R
Voltage output
R
Unit
Scaling
Range or On/Off
factor
text
ms
1
0 - 65535
-
1
-
%
100
0.00 - 100.00
-
1
0 - 1
-
1
0 - 1
-
1
0 - 1
-
1
0 - 1
%
100
-200.0 - 200.0
-
1
0 - 1
%
10
10.0 - 400.0
s
100
0.00 - 650.0
s
100
0.00 - 650.0
-
1
HIGH
-
1
HIGH
Hz
100
1.00 - 550.00
%
100
-200.0 - 200.0
%
100
-200.0 - 200.0
-
1000
0.000 - 65.000
s
1
0 - 60
-
1
0 - 60
%
100
0.00 - 500.00
-
100
0.00 - 60.00
Hz
100
-327.68 - 327.67
RPM 1
-16250 - 16250
A
100
0 - 163.83
Nm
100
-325.00 - 325.00
kW
100
0 - 327.67
kWh
1
0 - 32767
V
1
0 - 32767
Hz
100
-327.68 - 327.67
kW
100
0 - 327.67
V
1
0 - 32767
Communicating with the PLC
7.2 MODBUS communication
Read
Write
-
-
-
-
HSW
HSW
STW:3
STW:3
STW:11
STW:11
STW:0
STW:0
STW:7
STW:7
P2240
P2240
r0055.8
(BICO) P2200
P0640
P0640
P1120
P1120
P1121
P1121
LOW
r0747.0
(BICO) P0731
LOW
r0747.1
(BICO) P0732
P2000
P2000
P2291
P2291
P2292
P2292
P2280
P2280
P2285
P2285
P2274
P2274
P2269
P2269
P2265
P2265
r0024
r0024
r0022
r0022
r0027
r0027
r0031
r0031
r0032
r0032
r0039
r0039
r0026
r0026
r0020
r0020
r0206
r0206
r0025
r0025