Parameter list
8.2 Parameter list
Parameter
Function
P0292
Converter temperature
warning [°C]
Defines the temperature difference (in °C) between the overtemperature trip threshold (F4) and the warn-
ing threshold (A504) of the converter. The trip threshold is stored internally by the converter and cannot be
changed by the user.
P0294
Converter I
Defines the [%] value at which warning A505 (converter I
Converter I
The I
t calculation value is deemed = 100 % when this maximum tolerable period is reached.
2
Dependency:
The output current of the converter has been reduced.
The value of I
Note:
P0294 = 100 % corresponds to stationary nominal load.
P0295
Converter fan off delay time
[s]
Defines converter fan switch-off delay time in seconds after converter has stopped.
Note:
Setting to 0, converter fan will switch off when the converter stops, that means no delay.
P0301[0...2]
Easy motor data, rated
motor power [kW]
Rated motor power from the rating plate. No other data is necessary. If this parameter is used, the rest of
the motor data are then estimated by the firmware.
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
Caution:
This functionality is only valid with 50 Hz supply, star configuration on 4-pole motors. You must set this
parameter to zero if you desire to set the other motor data.
P0304[0...2]
Rated motor voltage [V]
Nominal motor voltage from rating plate.
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
Default value is depending on converter type and its rating data.
Caution:
The input of rating plate data must correspond with the wiring of the motor (star/delta). This means, if delta
wiring is used for the motor, delta rating plate data has to be entered.
214
Range
0 - 25
t warning [%]
10.0 - 100.0
2
t calculation is used to determine a maximum tolerable period for converter overload.
2
t does not exceed 100 %.
2
0 - 3600
0 - 2000
10 - 2000
Factory
Can be
Scaling
default
changed
5
U, T
-
95.0
U, T
-
t) is generated.
2
0
U, T
-
0
C(1)
-
400
C(1)
-
Operating Instructions, 10/2019, A5E34559884-012
Data
Data
Acc.
set
type
Level
-
U16
3
-
Float
3
-
U16
3
DDS
Float
1
DDS
U16
1