Parameter list
8.2 Parameter list
Parameter
Function
3-wire control
using STOP as permanent signal, FWD and REVP as pulses
3 wire control
using OFF1/HOLD and REV as permanent signal, ON as pulse signal
0
1
2
3
Note:
Where:
P denotes Pulse
FWD denotes FORWARD
REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 -
P0704) are redefined as follows:
Settings of
P0701 - P0706
= 1 (P0840)
= 2 (P0842)
= 12 (P1113)
To use the 2/3-wire control, the sources for ON/OFF1 (P0840), ON_REV/OFF1 (P0842) and REV (P1113)
corresponding to the redefined values have to be set accordingly.
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
Regarding the use of fixed frequencies see P1000 and P1001.
228
Range
Siemens (start/dir)
2-wire (fwd/rev)
3-wire (fwd/rev)
3-wire (start/dir)
P0727 = 0 (Siemens
Standard Control)
ON/OFF1
ON_REV/OFF1
REV
Factory
Can be
Scaling
default
changed
P0727 = 1 (2-
P0727 = 2 (3-wire
wire Control)
Control)
ON_FWD
STOP
ON_REV
FWDP
REV
REVP
Operating Instructions, 10/2019, A5E34559884-012
Data
Data
Acc.
set
type
Level
P0727 = 3 (3-wire
Control)
ON_PULSE
OFF1/HOLD
REV
SINAMICS V20 Converter