Parameter
Function
r0955[0...2]
CO/BO: Status word 2 at
fault
Displays status word 2 when the first instantaneous fault occurs (see r0053).
Index:
[0]
[1]
[2]
Note:
Only one set of fault information is stored per block of instantaneous faults. r0955[0] corresponds to
r0947[0...7], r0955[1] corresponds to r0947[8...15] and r0955[2] corresponds to r0947[16...23].
r0956[0...2]
CO: DC-link voltage at
fault [V]
Displays the DC link voltage when the first instantaneous fault occurs (see r0026).
Index:
[0]
[1]
[2]
Note:
Only one set of fault information is stored per block of instantaneous faults. r0956[0] corresponds to
r0947[0...7], r0956[1] corresponds to r0947[8...15] and r0956[2] corresponds to r0947[16...23].
r0957[0...2]
CO: Act. output current
at fault [A]
Displays the output current RMS when the first instantaneous fault occurs (see r0027).
Index:
[0]
[1]
[2]
Note:
Only one set of fault information is stored per block of instantaneous faults. r0957[0] corresponds to
r0947[0...7], r0957[1] corresponds to r0947[8...15] and r0957[2] corresponds to r0947[16...23].
r0958[0...2]
CO: Act. output voltage
at fault [V]
Displays the output voltage when the first instantaneous fault occurs (see r0025).
Index:
[0]
[1]
[2]
Note:
Only one set of fault information is stored per block of instantaneous faults. r0958[0] corresponds to
r0947[0...7], r0958[1] corresponds to r0947[8...15] and r0958[2] corresponds to r0947[16...23].
r0964[0...6]
Firmware version data
Firmware version data.
Index:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
r0967
Control word 1
Displays control word 1. See r0054 for the bit field description.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
-
-
Recent trip - Fault information
Recent trip - 1 Fault information
Recent trip - 2 Fault information
-
-
Recent trip - Fault information
Recent trip - 1 Fault information
Recent trip - 2 Fault information
-
-
Recent trip - Fault information
Recent trip - 1 Fault information
Recent trip - 2 Fault information
-
-
Recent trip - Fault information
Recent trip - 1 Fault information
Recent trip - 2 Fault information
-
-
Company (Siemens = 42)
Product type (V20 = 8001)
Firmware version
Firmware date (year)
Firmware date (day/month)
Number of converter objects
Firmware version
-
-
Can be
Scaling
Data
changed
set
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U16
3
Float
3
Float
3
Float
3
U16
3
U16
3
241