Parameter list
8.2 Parameter list
Parameter
Function
P1175[0...2]
BI: Dual ramp enable
Defines command source of dual ramp enable command. If binary input is equal to one, then the dual
ramp will be applied. This works as follows:
Ramp-up:
Converter starts ramp-up using ramp time from P1120
When f_act > P2157, switch to ramp time from P1060
Ramp-down:
Converter starts ramp-down using ramp time from P1061
When f_act < P2159, switch to ramp time from P1121
Dependency:
See P2150, P2157, P2159, r2198.
Note:
The dual ramp algorithm uses r2198 bits 1 and 2 to determine (f_act > P2157) and (f_act < P2159). P2150
is used to apply hysteresis to these settings, so the user may wish to change the value of this parameter
to make the dual ramp function more responsive. It is not recommended that the dual ramp function is
used in conjunction with JOG ramp.
See P1124.
r1199.7...12
CO/BO: RFG status
word
Displays status of ramp function generator (RFG).
Bit
07
08
09
10
11
12
Note:
See P2157 and P2159.
258
Range
0 - 4294967295
-
Signal name
Ramp #0 active
Ramp #1 active
Ramping finished
Direction right/left
f_act > P2157(f_2)
f_act < P2159(f_3)
Factory
Can be
default
changed
0
T
-
-
Operating Instructions, 10/2019, A5E34559884-012
Scaling
Data
Data
set
type
-
CDS
U32
-
-
U16
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
SINAMICS V20 Converter
Acc.
Level
3