Parameter
Function
P2001[0...2]
Reference voltage [V]
Full-scale output voltage (i.e. 100 %) used over serial link (corresponds to 4000H).
Example:
Note:
Changes to P2001 result in a new calculation of P2004.
P2002[0...2]
Reference current [A]
Full-scale output current used over serial link (corresponds to 4000H).
Example:
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. A) values) may differ. In this case an automatic conversion to the target value is made.
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
Note:
Changes to P2002 result in a new calculation of P2004.
P2003[0...2]
Reference torque [Nm]
Full-scale reference torque used over the serial link (corresponds to 4000H).
Example:
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. Nm) values) may differ. In this case an automatic conversion to the target value is made.
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
Note:
Changes to P2003 result in a new calculation of P2004.
P2004[0...2]
Reference power
Full-scale reference power used over the serial link (corresponds to 4000H).
Example:
If a BICO connection is made between two parameters, the 'unit' of the parameters (standardized (Hex) or
physical (i.e. kW/hp) values) may differ. In this case an automatic conversion to the target value is made.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
10 - 2000
1000
0.10 - 10000.0
0.10
0.10 - 99999.0
0.75
0.01 - 2000.0
0.75
Can be
Scaling
Data
changed
set
T
-
DDS
T
-
DDS
T
-
DDS
T
-
DDS
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U16
3
Float 3
Float 3
Float 3
279