Parameter list
8.2 Parameter list
Parameter
Function
P2101[0...2]
Stop reaction value
Sets converter stop reaction values for faults selected by P2100 (alarm number selection). This indexed
parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
0
1
2
3
4
Index:
[0]
[1]
[2]
Note:
Settings 1 - 3 are only available for fault codes.
Setting 4 is only available for warnings.
Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[0...2]
BI: 1. Faults acknowl-
edgement
Defines first source of fault acknowledgement.
Setting:
722.0
722.1
722.2
P2104[0...2]
BI: 2. Faults acknowl-
edgement
Selects second source of fault acknowledgement.
Setting:
See P2103
P2106[0...2]
BI: External fault
Selects source of external faults.
Setting:
See P2103
r2110[0...3]
CO: Warning number
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be
viewed.
Index:
[0]
[1]
[2]
[3]
Notice:
Indices 0 and 1 are not stored.
Note:
The LED indicates the warning status in this case. The keypad will flash while a warning is active.
P2111
Total number of warnings
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
290
Range
Factory
default
0 - 4
0
No reaction, no display
OFF1 stop reaction
OFF2 stop reaction
OFF3 stop reaction
No reaction, warning only
Stop reaction value 1
Stop reaction value 2
Stop reaction value 3
0 - 4294967295
722.2
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
0 - 4294967295
0
0 - 4294967295
1
-
-
Recent Warnings --, warning 1
Recent Warnings --, warning 2
Recent Warnings -1, warning 3
Recent Warnings -1, warning 4
0 - 4
0
Can be
Scaling
Data
changed
set
T
-
-
T
-
CDS
T
-
CDS
T
-
CDS
-
-
-
T
-
-
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Data
Acc.
type
Level
U16
3
U32
3
U32
3
U32
3
U16
2
U16
3