Siemens SINAMICS V20 Operating Instructions Manual page 72

Low voltage converters
Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.5 Quick commissioning
Connection macro Cn004 - Fixed speeds in binary mode
Fixed speeds with ON command in binary mode
Up to 16 different fixed frequency values (0 Hz, P1001 to P1015) can be selected by the
fixed frequency selectors (P1020 to P1023). For more information about the fixed
frequencies in binary mode, see the parameter descriptions of P1001 to P1016 in Section
"Parameter list (Page 198)".
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1003[0]
Fixed frequency 3
P1004[0]
Fixed frequency 4
P1016[0]
Fixed frequency mode
P0840[0]
BI: ON/OFF1
P1020[0]
BI: Fixed frequency selection bit 0
P1021[0]
BI: Fixed frequency selection bit 1
P1022[0]
BI: Fixed frequency selection bit 2
P1023[0]
BI: Fixed frequency selection bit 3
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
70
Factory default
Default for Cn004 Remarks
1
2
1
3
0
15
0
16
9
17
15
18
10
10
15
15
25
25
50
50
1
2
19.0
1025.0
722.3
722.0
722.4
722.1
722.5
722.2
722.6
722.3
21
21
52.3
52.2
52.7
52.3
Terminals as command source
Fixed frequency
Fixed speed bit 0
Fixed speed bit 1
Fixed speed bit 2
Fixed speed bit 3
Fixed speed 1
Fixed speed 2
Fixed speed 3
Fixed speed 4
Binary mode
Converter starts at the fixed speed
selected
DI1
DI2
DI3
DI4
Actual frequency
Converter running
Converter fault active
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012