Siemens SINAMICS V20 Operating Instructions Manual page 80

Low voltage converters
Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.5 Quick commissioning
Setting application macros
Application macro AP010 - Simple pump applications
Parameter Description
P1080[0]
Minimum frequency
P1300[0]
Control mode
P1110[0]
BI: Inhibit negative frequen-
cy setpoint
P1210[0]
Automatic restart
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
Application macro AP020 - Simple fan applications
Parameter Description
P1110[0]
BI: Inhibit negative frequency
setpoint
P1300[0]
Control mode
P1200[0]
Flying start
P1210[0]
Automatic restart
P1080[0]
Minimum frequency
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
78
Factory
Default for
default
AP010
0
15
0
7
0
1
1
2
10
10
10
10
Factory
Default for
default
AP020
0
1
0
7
0
2
1
2
0
20
10
10
10
20
Remarks
Converter running at a lower speed inhibited
Quadratic V/f
Reverse pump rotation inhibited
Restart after mains blackout
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero
Remarks
Reverse fan rotation inhibited
Quadratic V/f
Search for the speed of the running motor with a
heavy inertia load so that the motor runs up to the
setpoint
Restart after mains blackout
Converter running at a lower speed inhibited
Ramp-up time from zero to maximum frequency
Ramp-down time from maximum frequency to zero
Operating Instructions, 10/2019, A5E34559884-012
SINAMICS V20 Converter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: