Restrictions on the estimated quick commissioning:
– This functionality is recommended at the rated supply voltage.
– This functionality is designed around the data for Siemens motors 1LE0001, 1TL0001,
– This functionality gives an estimate of the motor data values; however, if the motor is
– The value calculations only work with motors connected in star configuration and
– The calculations use the DC link voltage measurement and thus only work if mains is
– The calculations are accurate only for 4-pole motors.
– The 87 Hz characteristic is not supported.
Setting parameters
Note
In the table below, "●" indicates that you must enter the value of this parameter according to
the rating plate of the motor when you carry out the conventional quick commissioning.
Parameters for
Parameters for
conventional
estimated quick
quick commis-
commissioning
sioning
P0003 = 3
P0003 = 3
P0010 = 1
P0010 = 1
P0100
P0100 = 0
P0301 = 0
P0301 > 0
P0304[0] ●
-
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
1LE1 and 1LA7 although it may make reasonable approximations for other motor
types.
to operate near the limits of its capability (rated power and current), then you must
carry out the conventional quick commissioning.
assume the supply frequency is 50 Hz.
connected.
Function
User access level
Commissioning parameter = 1 (quick commissioning)
50/60 Hz selection
Rated motor power [kW]
Rated motor voltage [V]
Commissioning via the built-in BOP
Setting
= 3 (Expert access level)
Set a value, if necessary:
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
Note:
Set this parameter to 0 if you want to carry out the esti-
mated quick commissioning.
Range: 0 to 2000
= 0: Conventional quick commissioning (factory default)
> 0: Estimated quick commissioning
Once you set this parameter to a non-zero value, you
only need to enter the rated motor power and then the
converter calculates and sets the values of the rest of
the motor data (P0304, P0305, P0307, P0308, P0310
and P0311).
Range: 10 to 2000
Note:
The input of rating plate data must correspond with the
wiring of the motor (star/delta).