Parameter
Function
Index:
See r0752
Notice:
Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of analog
input scaling) are positive or negative respectively. However, deadband is active in both directions from
point of intersection (x axis with analog input scaling curve), if sign of P0758 and P0760 are opposite.
Note:
P0761[x] = 0: No deadband active.
Minimum frequency P1080 should be zero when using center zero setup.
There is no hysteresis at the end of the deadband.
P0762[0...1]
Delay for loss of signal
action [ms]
Defines time delay between loss of analog setpoint and appearance of fault code F80.
Index:
See r0752
Note:
Expert users can choose the desired reaction to F80 (default is OFF2).
r0770
Number of analog output -
Displays number of analog outputs available.
P0771[0]
CI: Analog output
Defines function of the analog output.
Index:
[0]
Setting:
21
24
25
26
27
P0773[0]
Smooth time analog
output [ms]
Defines smoothing time for analog output signal. This parameter enables smoothing for analog output
using a PT1 filter.
Index:
See P0771
Dependency:
P0773 = 0: Deactivates filter.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
0 - 10000
10
-
0 - 4294967295
21[0]
Analog output 1 (AO1)
CO: Actual frequency (scaled to P2000)
CO: Actual output frequency (scaled to P2000)
CO: Actual output voltage (scaled to P2001)
CO: Actual DC-link voltage (scaled to P2001)
CO: Actual output current (scaled to P2002)
0 - 1000
2
Can be
Scaling
Data
changed
set
U, T
-
-
-
-
-
U, T
-
-
U, T
-
-
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U16
3
U16
3
U32
2
U16
2
233