Parameter
Function
Dependency:
Following physical values influence the converter overload protection (see diagram):
Heat sink temperature (r0037[0]); causes A504 and F4.
IGBT Junction temperature (r0037[1]); causes F4 or F6.
Delta temperature between heat sink and junction temperature; causes A504 and F6.
Converter I
Notice:
P0290 = 0, 2:
Reduction of output frequency is only effective if the load is also reduced.
This is for example valid for light overload applications with a quadratic torque characteristic as pumps or fans.
For settings P0290 = 0 or 2, the I-max controller will act upon the output current limit (r0067) in case of
overtemperature.
P0290 = 0:
With pulse frequencies above nominal, pulse frequency will be reduced to nominal immediately in the
event of r0027 greater than r0067 (current limit).
P0290 = 2, 3:
The pulse frequency P1800 is reduced only if higher than 2 kHz and if the operating frequency is below 2 Hz.
The actual pulse frequency is displayed in r1801[0] and the minimal pulse frequency for reduction is
displayed in r1801[1].
Converter I
A trip will always result, if the action taken does not sufficiently reduce internal temperatures.
P0291[0...2]
Converter protection
Bit 00 for enabling/disabling automatic pulse frequency reduction at output frequencies below 2 Hz. The
benefit is to reduce the noises at frequencies below 2 Hz.
Bit
00
01
02
03
04
05
Note:
See P0290
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
t (r0036); causes A505 and F5.
2
t acts upon output current and output frequency, but not on pulse frequency.
2
0 - 7
Signal name
Pulse frequency reduced below 2 Hz
Reserved
Phase loss detection enable
Reserved
Output current ripple detection enable
Enhanced dead-time compensation enable
Factory
Can be
Scaling
default
changed
1
U, T
-
1 signal
Yes
Yes
No
Yes
No
No
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
DDS
U16
4
0 signal
No
No
Yes
No
Yes
Yes
213