Siemens SINAMICS V20 Operating Instructions Manual page 74

Low voltage converters
Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.5 Quick commissioning
Parameter Description
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1074[0]
BI: Disable additional setpoint
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
Connection macro Cn006 - External push button control
Note that the command sources are pulse signals.
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P0727[0]
Selection of 2/3-wire method
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
P1040[0]
Setpoint of the MOP
P1047[0]
MOP ramp-up time of the RFG
P1048[0]
MOP ramp-down time of the RFG
72
Factory default
Default for Cn005 Remarks
10
10
15
15
0
1025.0
21
21
52.3
52.2
52.7
52.3
Factory default
Default for Cn006 Remarks
1
2
1
1
0
2
0
1
9
13
15
14
0
3
21
21
52.3
52.2
52.7
52.3
5
0
10
10
10
10
Fixed speed 1
Fixed speed 2
FF disables the additional setpoint
Actual frequency
Converter running
Converter fault active
Terminals as command source
MOP as setpoint
OFF1/hold
ON pulse
MOP up pulse
MOP down pulse
3-wire
ON pulse + OFF1/hold + Reverse
Actual frequency
Converter running
Converter fault active
Initial frequency
Ramp-up time from zero to maxi-
mum frequency
Ramp-down time from maximum
frequency to zero
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012