Communicating with the PLC
7.1 USS communication
No.
Description
101
Parameter is currently deactivated; parameter has no function in the present converter status
102
Communication channel width is insufficient for response; dependent on the number of PKW and the maximum
net data length of the converter
104
Illegal parameter value
105
Parameter is indexed
106
Request is not included/task is not supported
109
PKW request access timeout/number of retries is exceeded/wait for response from CPU side
110
Parameter value cannot be changed (parameter is locked)
200/201
Changed lower/upper limits exceeded
202/203
No display on the BOP
204
The available access authorization does not cover parameter changes
300
Array elements differ
Basic converter settings
Parameter
Function
P0010
Commissioning parameter
P0970
Factory reset
P0003
User access level
P0700
Selection of command source
P1000
Selection of frequency setpoint
P2023
RS485 protocol selection
P2010[0]
USS/MODBUS baudrate
P2011[0]
USS address
P2012[0]
USS PZD (process data) length
178
Setting
= 30: restores to factory settings
Possible settings:
= 1: resets all parameters (not user defaults) to their default
values
= 21: resets all parameters and all user defaults to factory
reset state
Note: Parameters P2010, P2011, P2023 retain their values after
a factory reset.
= 3
= 5: USS/MODBUS on RS485
Factory default: 1 (operator panel)
= 5: USS/MODBUS on RS485
Factory default: 1 (MOP setpoint)
= 1: USS (factory default)
Note: After changing P2023, powercycle the converter. During the
powercycle, wait until LED has gone off or the display has gone
blank (may take a few seconds) before re-applying power. If
P2023 has been changed via a PLC, make sure the change has
been saved to EEPROM via P0971.
Possible settings:
= 6: 9600 bps (factory default)
= 7: 19200 bps
= 8: 38400 bps
...
= 12: 115200 bps
Sets the unique address for the converter.
Range: 0 to 31 (factory default: 0)
Defines the number of 16-bit words in PZD part of USS telegram.
Range: 0 to 8 (factory default: 2)
Operating Instructions, 10/2019, A5E34559884-012