Parameter
Function
P2186[0...2]
Lower torque threshold 1
[Nm]
Lower limit threshold value 1 for comparing actual torque.
Dependency:
See P2181 for calculated default value.
P2187[0...2]
Upper torque threshold 2
[Nm]
Upper limit threshold value 2 for comparing actual torque.
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
Note:
See P2185
P2188[0...2]
Lower torque threshold 2
[Nm]
Lower limit threshold value 2 for comparing actual torque.
Dependency:
See P2181 for calculated default value.
P2189[0...2]
Upper torque threshold 3
[Nm]
Upper limit threshold value 3 for comparing actual torque.
Dependency:
This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
Note:
See P2185
P2190[0...2]
Lower torque threshold 3
[Nm]
Lower limit threshold value 3 for comparing actual torque.
Dependency:
See P2181 for calculated default value.
P2192[0...2]
Load monitoring delay time
[s]
P2192 defines a delay before warning/trip becomes active.
- It is used to eliminate events caused by transient conditions.
- It is used for both methods of fault detection.
r2197.0...12
CO/BO: Monitoring word 1
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
0.0 - 99999.0
0.0 - 99999.0
0.0 - 99999.0
0.0 - 99999.0
0.0 - 99999.0
0 - 65
-
Signal name
|f_act| <= P1080 (f_min)
|f_act| <= P2155 (f_1)
|f_act| > P2155 (f_1)
f_act >= zero
f_act >= setp. (f_set)
|f_act| <= P2167 (f_off)
|f_act| >= P1082 (f_max)
f_act == setp. (f_set)
Act. current |r0027| >= P2170
Act. unfilt. Vdc < P2172
Act. unfilt. Vdc > P2172
Output load is not present
|f_act| > P1082 with delay
Factory
Can be
Scaling
default
changed
0.0
U, T
-
U, T
-
Value in
r0333
0.0
U, T
-
Value in
U, T
-
r0333
0.0
U, T
-
10
U, T
-
-
-
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
U16
3
-
U16
3
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
295