Commissioning via the built-in BOP
5.5 Quick commissioning
Connection macro Cn010 - USS control
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P2023[0]
RS485 protocol selection
P2010[0]
USS/MODBUS baudrate
P2011[0]
USS address
P2012[0]
USS PZD length
P2013[0]
USS PKW length
P2014[0]
USS/MODBUS telegram off time
Connection macro Cn011 - MODBUS RTU control
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P2023[0]
RS485 protocol selection
76
Factory default
1
1
1
6
0
2
127
2000
Factory default
Default for Cn011 Remarks
1
5
1
5
1
2
Default for Cn010 Remarks
5
RS485 as the command source
5
RS485 as the speed setpoint
1
USS protocol
8
Baudrate 38400 bps
1
USS address for converter
2
Number of PZD words
127
Variable PKW words
500
Time to receive data
RS485 as the command source
RS485 as the speed setpoint
MODBUS RTU protocol
Operating Instructions, 10/2019, A5E34559884-012
SINAMICS V20 Converter