SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Function
Minimum frequency [Hz]
Maximum frequency [Hz]
Ramp-up time [s]
Ramp-down time [s]
Control mode
End of quick commission-
ing
Select motor data identifi-
cation
Commissioning via the built-in BOP
Setting
Range: 0.00 to 550.00 (factory default: 0.00)
Note:
The value set here is valid for both clockwise and coun-
ter-clockwise rotation.
Range: 0.00 to 550.00 (factory default: 50.00)
Note:
The value set here is valid for both clockwise and coun-
ter-clockwise rotation
Range: 0.00 to 650.00 (factory default: 10.00)
Note:
The value set here means the time taken for motor to
accelerate from standstill up to the maximum motor
frequency (P1082) when no rounding is used.
Range: 0.00 to 650.00 (factory default: 10.00)
Note:
The value set here means the time taken for motor to
decelerate from the maximum motor frequency (P1082)
down to standstill when no rounding is used.
= 0: V/f with linear characteristic (factory default)
= 1: V/f with FCC
= 2: V/f with quadratic characteristic
= 3: V/f with programmable characteristic
= 4: V/f with linear eco
= 5: V/f for textile applications
= 6: V/f with FCC for textile applications
= 7: V/f with quadratic eco
= 19: V/f control with independent voltage setpoint
= 0: No quick commissioning (factory default)
= 1: End quick commissioning with factory reset
= 2: End quick commissioning
= 3: End quick commissioning and initiate motor data
calculation
Note:
After completion of calculation, P3900 and P0010 are
automatically reset to their original value 0.
The converter displays "8.8.8.8.8" which indicates that it
is busy with internal data processing.
= 0: Disabled (factory default)
= 2: Identification of all parameters in standstill
5.5 Quick commissioning
83