Parameter
Function
P2360[0...2]
Enable cavitation protec-
tion
Cavitation protection enabled.
Will generate a fault/warning when cavitation conditions are deemed to be present.
0
1
2
P2361[0...2]
Cavitation threshold [%]
Feedback threshold over which a fault/warning is triggered, as a percentage (%).
P2362[0...2]
Cavitation protection time [s]
The time for which cavitation conditions have to be present before a fault/warning is triggered.
P2365[0...2]
Hibernation enable/disable
Select or disable the hibernation functionality.
0
1
2
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
0 - 2
0
Disable
Fault
Warn
0.00 - 200.00
40.00
0 - 65000
30
0 - 2
0
Disabled
Frequency hibernation (The converter uses the frequency setpoint as the
wakeup trigger. You can use P2366 and P2367 to configure this function.)
PID hibernation (The converter uses the PID error as the wakeup trigger. You
can use P2390, P2391, and P2392 to configure this function.)
Can be
Scaling
Data
changed
set
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U16
2
Float
2
U16
2
U16
2