Parameter
Function
P2167[0...2]
Switch-off frequency f_off
[Hz]
Defines the threshold of the monitoring function |f_act| > P2167 (f_off). P2167 influences following func-
tions:
If the actual frequency falls below this threshold and the time delay has expired, bit 1 in status word 2
(r0053) is reset.
If an OFF1 or OFF3 was applied and bit 1 is reset the converter will disable the pulse (OFF2).
P2168[0...2]
Delay time T_off [ms]
Defines time for which the converter may operate below switch-off frequency (P2167) before switch off
occurs.
Dependency:
Active if holding brake (P1215) not parameterized.
P2170[0...2]
Threshold current I_thresh
[%]
Defines threshold current relative to P0305 (rated motor current) to be used in comparisons of I_act and
I_Thresh. This threshold controls bit 3 in status word 3 (r0053).
P2171[0...2]
Delay time current [ms]
Defines delay time prior to activation of current comparison.
P2172[0...2]
Threshold DC-link voltage
[V]
Defines DC link voltage to be compared to actual voltage. This voltage controls bits 7 and 8 in status word
3 (r0053).
P2173[0...2]
Delay time DC-link volt-
age [ms]
Defines delay time prior to activation of threshold comparison.
P2177[0...2]
Delay time for motor is
blocked [ms]
Delay time for identifying that the motor is blocked.
P2179
Current limit for no load
identified [%]
Threshold current for A922 (no load applied to converter) relative to P0305 (rated motor current).
Notice:
If a motor setpoint cannot be entered and the current limit (P2179) is not exceeded, warning A922 (no
load applied) is issued when delay time (P2180) expires.
Note:
It may be that the motor is not connected or a phase could be missing.
P2180
Delay time for no-load
detection [ms]
Delay time for detecting a missing output load.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
0.00 - 10.00
1.00
0 - 10000
0
0.00 - 400.0
100.0
0 - 10000
10
0 - 2000
800
0 - 10000
10
0 - 10000
10
0.00 - 10.0
3.0
0 - 10000
2000
Can be
Scaling
Data
changed
set
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
-
U, T
-
-
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
Float
3
U16
3
Float
3
U16
3
U16
3
U16
3
U16
3
Float
3
U16
3
293