Dependency:
P0719 has higher priority than P0700 and P1000. If set to a value other than 0 (i.e. BICO parameter is not
the setpoint source), P0844/P0848 (first source of OFF2/OFF3) are not effective; instead, P0845/P0849
(second source of OFF2/OFF3) apply and the OFF commands are obtained via the particular source
defined. BICO connections made previously remain unchanged.
Notice:
Particularly useful when e.g. changing command source temporarily from P0700 = 2. Settings in P0719
(contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
r0720
Number of digital inputs
Displays number of digital inputs.
r0722.0...12
CO/BO: Digital input
values
Displays status of digital inputs.
Bit
00
01
02
03
04
05
11
12
Note:
Segment is lit when signal is active.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P0724
Debounce time for digital
inputs
Defines debounce time (filtering time) used for digital inputs.
0
1
2
3
226
Range
Cmd = USS on RS232 (reserved), Setpoint = USS/MODBUS on RS485
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
Cmd = USS/MODBUS on RS485, Setpoint = BICO parameter
Cmd = USS/MODBUS on RS485, Setpoint = MOP setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Fixed frequency
Cmd = USS/MODBUS on RS485, Setpoint = USS on RS232 (reserved)
Cmd = USS/MODBUS on RS485, Setpoint = USS/MODBUS on RS485
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint 2
-
-
Signal name
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Analog input 1
Analog input 2
0 - 3
No debounce time
2.5 ms debounce time
8.2 ms debounce time
12.3 ms debounce time
Factory
Can be
Scaling
default
changed
-
-
-
-
-
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
3
T
-
Operating Instructions, 10/2019, A5E34559884-012
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
2
0 signal
No
No
No
No
No
No
No
No
-
U16
3
SINAMICS V20 Converter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents