Connection macro Cn009 - PID control with the fixed value reference
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P2200[0]
BI: Enable PID controller
P2201[0]
Fixed PID setpoint 1 [%]
P2202[0]
Fixed PID setpoint 2 [%]
P2203[0]
Fixed PID setpoint 3 [%]
P2216[0]
Fixed PID setpoint mode
P2220[0]
BI: Fixed PID setpoint select bit 0 722.3
P2221[0]
BI: Fixed PID setpoint select bit 1 722.4
P2222[0]
BI: Fixed PID setpoint select bit 2 722.5
P2253[0]
CI: PID setpoint
P2264[0]
CI: PID feedback
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Factory default
Default for Cn009
1
2
0
1
0
15
9
16
15
17
0
1
10
10
20
20
50
50
1
1
722.1
722.2
722.3
0
2224
755.0
755.1
Commissioning via the built-in BOP
5.5 Quick commissioning
Remarks
Terminals as command source
ON/OFF
DI2 = PID fixed value 1
DI3 = PID fixed value 2
DI4 = PID fixed value 3
Enable PID
-
-
-
Direct selection
BICO connection DI2
BICO connection DI3
BICO connection DI4
PID setpoint = fixed value
PID feedback = AI2