Parameter Description
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
Connection macro Cn003 - Fixed speeds
Three fixed speeds with ON/OFF1
If more than one fixed frequency is selected at the same time, the selected frequencies are
summed, that is, FF1 + FF2 + FF3.
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P1016[0]
Fixed frequency mode
P1020[0]
BI: Fixed frequency selection bit 0
P1021[0]
BI: Fixed frequency selection bit 1
P1022[0]
BI: Fixed frequency selection bit 2
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1003[0]
Fixed frequency 3
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Factory default
Default for Cn002
21
21
52.3
52.2
52.7
52.3
Factory default
1
1
0
0
9
15
1
722.3
722.4
722.5
10
15
25
21
52.3
52.7
Commissioning via the built-in BOP
5.5 Quick commissioning
Remarks
Actual frequency
Converter running
Converter fault active
Default for Cn003 Remarks
2
Terminal as command source
3
Fixed frequency
1
ON/OFF
15
Fixed speed bit 0
16
Fixed speed bit 1
17
Fixed speed bit 2
1
Direct selection mode
722.1
DI2
722.2
DI3
722.3
DI4
10
Speed low
15
Speed middle
25
Speed high
21
Actual frequency
52.2
Converter running
52.3
Converter fault active
69