Commissioning via the built-in BOP
5.1 The built-in Basic Operator Panel (BOP)
Button functions
Stops the converter
Single press
Double press (< 2 s) or
long press ( > 3 s)
Starts the converter
If the converter is started in HAND/JOG/AUTO mode, the converter running icon (
Exception:
This button is inactive when the converter is configured for control from terminals or USS/MODBUS on
RS485 (P0700=2 or P0700=5) in AUTO mode.
Multi-function button
Short press ( < 2 s)
Long press ( > 2 s)
Short press ( < 2 s)
Long press ( > 2 s)
Hand/Jog/Auto
Press to switch between different modes:
+
Note:
Jog mode is only available if the motor is stopped.
54
OFF1 stop reaction: the converter brings the motor to a standstill in the
ramp-down time set in parameter P1121.
Exception:
The button is inactive if the converter is configured for control from terminals
or USS/MODBUS on RS485 (P0700=2 or P0700=5) in AUTO mode.
OFF2 stop reaction: the converter allows the motor to coast to a standstill
without using any ramp-down times.
Enters the parameter setting menu or moves to the next screen in the
•
setup menu
Restarts the digit by digit editing on the selected item
•
Returns to the fault code display
•
If pressed twice in digit by digit editing, returns to the previous screen
•
without changing the item being edited
Returns to the status screen
•
Enters the setup menu
•
Switches between status values
•
Enters edit value mode or change to the next digit
•
Clears faults
•
Returns to the fault code display
•
Quick parameter number or value edit
•
Accesses fault information data
•
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
) appears.