Technical specifications
Overload capability
Power rating (kW)
0.12 to 15
18.5 (HO)/22 (HO)
22 (LO)/30 (LO)
EMC requirements
Note
Install all converters in accordance with the manufacturer's guidelines and in accordance
with good EMC practices.
Use copper screened cable. For the maximum motor cable lengths, refer to Section
"Terminal description (Page 40)".
Do not exceed the default switching frequency.
ESD
Radiated immunity
Burst
Surge
Conducted immunity
Voltage distortion immunity
Conducted emissions
Radiated emissions
Maximum power losses
Three phase AC 400 V converters
Frame size
Power
(kW)
rating
(hp)
Maximum power loss (w)
1)
With I/O fully loaded
1)
Single phase AC 230 V converters
Frame size
FSAA/FSAB
Power
(kW)
0.12
rating
(hp)
0.17
Maximum power
14
loss (w)
1)
With I/O fully loaded
1)
346
Average output current
100% rated
Three phase AC 400 V converters
EN 61800-3
Three phase AC 400 V filtered converters:
EN 61800-3 Category C2/C3
FSA
0.37
0.55
0.75 1.1 1.5
0.75
0.75
1
1.5 2
25
28
33
43
0.25
0.37
0.55
0.33
0.5
0.75
22
29
39
Overload current
150% rated for 60 seconds
110% rated for 60 seconds
FSB
FSC
2.2 3
4
5.5
3
5
5
7.5
54
68
82
100
145
FSAC
0.75
1.1
1.5
1
1.5
2
48
57
87
Maximum overload cycle
150% rated for 60 seconds followed by
94.5% rated for 240 seconds
110% rated for 60 seconds followed by
more than 98% rated for 240 seconds
Single phase AC 230 V converters
EN 61800-3
Single phase AC 230 V filtered converters:
EN 61800-3 Category C1/C2
FSD
FSE
7.5
11
15
18.5 22
HO
10
15
20
25
HO
180 276 338 387
FSAD
2.2
3.0
3
4
138
177
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
22
30
LO
HO LO
30
30
40
LO
HO LO
475 457 626
FSC
2.2
3.0
3
4
138
177