Parameter
Function
r2053[0...7]
I/O Extension Module
identification
Displays identification data of the I/O Extension Module.
Index:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
r2067.0...12
CO/BO: Digital input
values status
Displays status of digital inputs.
Bit
00
01
02
03
04
05
11
12
Note:
This is used for BICO connection without software intervention.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P2100[0...2]
Alarm number selection
Selects up to 3 faults or alarms for non-default reactions.
Example:
If, for example, an OFF3 is to be carried out instead of an OFF2 for a fault, the fault number has to be
entered in P2100 and the desired reaction selected in P2101 (in this case (OFF3) P2101 = 3).
Index:
[0]
[1]
[2]
Note:
All fault codes have a default reaction to OFF2.
Only the following faults (F11,F12,F20,F35,F71,F72,F85,F200,F221,F222, and F452) can be changed
from the default reactions.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
-
I/O Extension Module ID number
I/O Extension Module firmware version number (major)
I/O Extension Module firmware version number (minor)
I/O Extension Module firmware version number (hot fix)
I/O Extension Module firmware version number (internal)
Not used
Not used
Company ID (Siemens = 42)
-
Signal name
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Digital input AI1
Digital input AI2
0 - 65535
Fault Number 1
Fault Number 2
Fault Number 3
Factory
Can be
Scaling
default
changed
0
-
-
-
-
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
0
T
-
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
3
0 signal
No
No
No
No
No
No
No
No
-
U16
3
289