Siemens SINAMICS V20 Operating Instructions Manual page 84

Low voltage converters
Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.5 Quick commissioning
Parameters for
Parameters for
conventional
estimated quick
quick commis-
commissioning
sioning
P0305[0] ●
-
P0307[0] ●
-
P0308[0] ●
-
P0309[0] ●
-
P0310[0] ●
-
P0311[0] ●
-
P0335[0]
P0335[0]
P0640[0]
P0640[0]
P0700[0]
P0700[0]
P1000[0]
P1000[0]
82
Function
Rated motor current [A]
Rated motor power
[kW/hp]
Rated motor power factor
(cosφ)
Rated motor efficiency [%] Range: 0.0 to 99.9
Rated motor frequency
[Hz]
Rated motor speed [RPM]
Motor cooling
Motor overload factor [%]
Selection of command
source
Selection of frequency
setpoint
Setting
Range: 0.01 to 10000
Note:
The input of rating plate data must correspond with the
wiring of the motor (star/delta).
Range: 0.01 to 2000.0
Note:
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
Range: 0.000 to 1.000
Note:
This parameter is visible only when P0100 = 0 or 2.
Note:
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
Range: 12.00 to 550.00
Range: 0 to 40000
Set according to the actual motor cooling method
= 0: Self-cooled (factory default)
= 1: Force-cooled
= 2: Self-cooled and internal fan
= 3: Force-cooled and internal fan
Range: 10.0 to 400.0 (factory default: 150.0)
Note:
The parameter defines motor overload current limit rela-
tive to P0305 (rated motor current).
= 0: Factory default setting
= 1: Operator panel (factory default)
= 2: Terminal
= 5: USS/MODBUS on RS485
Range: 0 to 77 (factory default: 1)
= 0: No main setpoint
= 1: MOP setpoint
= 2: Analog setpoint 1
= 3: Fixed frequency
= 5: USS/MODBUS on RS485
= 7: Analog setpoint 2
For additional settings, see Chapter "Parameter list
(Page 193)".
Operating Instructions, 10/2019, A5E34559884-012
SINAMICS V20 Converter