Scaling
Specification of the reference quantity with which the signal value will be converted
automatically.
Reference quantities, corresponding to 100 %, are required for the statement of physical
units as percentages. These reference quantities are entered in P2000 to P2004.
In addition to P2000 to P2004 the following normalizations are used:
● TEMP: 100 °C = 100 %
● PERCENT: 1.0 = 100 %
● 4000H: 4000 hex = 100 %
Can be changed
Converter state in which the parameter is changeable. Three states are possible:
● Commissioning: C, C(1) or C(30)
● Run: U
● Ready to run: T
This indicates when the parameter can be changed. One, two or all three states may be
specified. If all three states are specified, this means that it is possible to change this
parameter setting in all three converter states. C shows the parameter is changeable
whatever P0010 equals; C(1) shows that the parameter is changeable only when P0010 = 1;
C(30) shows that the parameter is changeable only when P0010 = 30.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Parameter list
8.1 Introduction to parameters