Parameter
Function
P1047[0...2]
MOP ramp-up time of
the RFG [s]
Sets the ramp-up time for the internal MOP ramp-function generator. The setpoint is changed from zero
up to limit defined in P1082 within this time.
Notice:
Refer to: P1048, P1082
P1048[0...2]
MOP ramp-down time of
the RFG [s]
Sets the ramp-down time for the internal MOP ramp-function generator. The setpoint is changed from limit
defined in P1082 down to zero within this time.
Notice:
Refer to: P1047, P1082
r1050
CO: Actual output freq.
of the MOP [Hz]
Displays output frequency of motor potentiometer setpoint.
P1055[0...2]
BI: Enable JOG right
Defines source of JOG right when P0719 = 0 (Auto selection of command/setpoint source).
P1056[0...2]
BI: Enable JOG left
Defines source of JOG left when P0719 = 0 (Auto selection of command/setpoint source).
P1057
JOG enable
While JOG enable is '0' Jogging (P1056 and P1055) is disabled. When '1' Jogging is enabled.
P1058[0...2]
JOG frequency [Hz]
Jogging increases the motor speed by small amounts. The JOG mode allows the operator to perform a
specific number of revolutions and position the rotor manually. In JOG mode, the RUN button on the op-
erator panel for jogging uses a non-latching switch on one of the digital inputs to control the motor speed.
While jogging, P1058 determines the frequency at which the converter will run. The motor speed is in-
creased as long as 'JOG left' or 'JOG right' are selected and until the left or right JOG frequency is
reached.
Dependency:
P1060 and P1061 set up and down ramp times respectively for jogging. Rounding times (P1130 - P1133),
rounding type (P1134) and P2167 will also have influence on the JOG ramp.
P1059[0...2]
JOG frequency left [Hz]
While JOG left is selected, this parameter determines the frequency at which the converter will run.
Dependency:
P1060 and P1061 set up and down ramp times respectively for jogging.
P1060[0...2]
JOG ramp-up time [s]
Sets jog ramp-up time. This is the time used while jogging is active.
Dependency:
See also P3350, P3353.
Notice:
Ramp times will be used as follows:
P1060/P1061 : JOG mode is active
P1120/P1121 : Normal mode (ON/OFF) is active
P1060/P1061 : Normal mode (ON/OFF) and P1124 is active
The rounding of P1130 - P1133 also applies to the JOG ramping.
Note:
If the SuperTorque function is enabled, the converter will initially ramp using the value in P3353.
P1061[0...2]
JOG ramp-down time [s]
Sets ramp-down time. This is the time used while jogging is active.
Dependency:
See also P3350, P3353.
Note:
See P1060
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Range
Factory
default
0.00 - 1000.00
10.00
0.00 - 1000.0
10.00
-
-
0 - 4294967295
19.8
0 - 4294967295
0
0 - 1
1
0.00 - 550.00
5.00
0.00 - 550.00
5.00
0.00 - 650.00
10.00
0.00 - 650.00
10.00
Can be
Scaling
Data
changed
set
U, T
-
DDS
U, T
-
DDS
-
-
-
T
-
CDS
T
-
CDS
T
-
-
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
Float
2
Float
2
Float
2
U32
3
U32
3
U16
3
Float
2
Float
2
Float
2
Float
2
251