Parameter list
8.2 Parameter list
Parameter
Function
P1070[0...2]
CI: Main setpoint
Defines source of main setpoint.
Setting:
755
1024
1050
P1071[0...2]
CI: Main setpoint scaling
Defines source of the main setpoint scaling.
Setting:
See P1070
P1074[0...2]
BI: Disable additional
setpoint
Disables additional setpoint.
Setting:
See P1070
P1075[0...2]
CI: Additional setpoint
Defines source of the additional setpoint (to be added to main setpoint).
Setting:
See P1070
P1076[0...2]
CI: Additional setpoint
scaling
Defines source of scaling for additional setpoint (to be added to main setpoint).
Setting:
1
755
1024
1050
r1078
CO: Total frequency
setpoint [Hz]
Displays sum of main and additional setpoints.
r1079
CO: Selected frequency
setpoint [Hz]
Displays selected frequency setpoint. Following frequency setpoints are displayed:
r1078 Total frequency setpoint
P1058 JOG frequency right
P1059 JOG frequency left
Dependency:
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.
Note:
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
P1080[0...2]
Minimum frequency [Hz]
Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The minimum
frequency P1080 represents a masking frequency of 0 Hz for all frequency target value sources e.g. ana-
log input, MOP, FF, USS with the exception of the JOG target value source (analogous to P1091). Thus
the frequency band +/-P1080 is run through in optimum time by means of the acceleration/deceleration
ramps. Dwelling in the frequency band is not possible. Furthermore, an overshoot of the actual frequency
f_act upper minimum frequency P1080 is output by the signal function |f_act| > f_min.
Note:
Value set here is valid both for clockwise and for counterclockwise rotation.
Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.
252
Range
Factory
default
0 - 4294967295
1050[0]
Analog input 1 setpoint
Fixed frequency setpoint
Motor potentiometer (MOP) setpoint
0 - 4294967295
1
0 - 4294967295
0
0 - 4294967295
0
0 - 4294967295
[0] 1
[1] 0
[2] 1
Scaling of 1.0 (100%)
Analog input 1 setpoint
Fixed frequency setpoint
MOP setpoint
-
-
-
-
0.00 - 550.00
0.00
Can be
Scaling
Data
changed
set
T
-
CDS
T
4000H
CDS
U, T
-
CDS
T
-
CDS
T
4000H
CDS
-
-
-
-
-
-
C, U, T
-
DDS
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Data
Acc.
type
Level
U32
3
U32
3
U32
3
U32
3
U32
3
Float
3
Float
3
Float
1