Electrical installation
4.2 Terminal description
User terminals
The illustration below takes the user terminal layout for FSA to FSE for example.
No.
Terminal
marking
1
10V
Analog inputs 2
AI1
3
AI2
Analog output 4
AO1
5
0V
6
P+
7
N-
44
Description
10 V output (tolerance ± 2% for the temperature range of 20 °C to 30 °C) referred to
0V, maximum 11 mA, short circuit protected
Mode:
Isolation to control circuit:
Voltage range:
Current range:
Voltage mode accuracy:
Current mode accuracy:
Input impedance:
Resolution:
Wire break detect:
Threshold 0 ⇒ 1 (used as DI):
Threshold 1 ⇒ 0 (used as DI):
Response time (digital input mode): 4 ms ± 4 ms
Mode:
Isolation to control circuit:
Current range:
Accuracy (0 mA to 20 mA):
Output capability:
Overall reference potential for RS485 communication and analog inputs/output
RS485 P +
RS485 N -
AI1: Single-ended, bipolar current and voltage
mode
AI2: Single-ended, unipolar current and voltage
mode
None
AI1: -10 V to 10 V; AI2: 0 V to 10 V
0 mA to 20 mA (4 mA to 20 mA - software se-
lectable)
± 1% full scale for the temperature range of
20 °C to 30 °C
± 1% full scale for the temperature range of
20 °C to 30 °C
Voltage mode: > 30 K
Current mode: 235 R
12-bit
Yes
4.0 V
1.6 V
Single-ended, unipolar current mode
None
0 mA to 20 mA (4 mA to 20 mA - software selectable)
± 0.5 mA for the temperature range of -10 °C to
60 °C
20 mA into 500 R