Parameter Function
P2948
Wobble signal increment step
P2949
Wobble signal pulse width [%]
5.6.3.14

Running the converter in motor staging mode

Functionality
Motor staging allows the control of up to 2 additional staged pumps or fans, based on a PID
control system. The complete system consists of one pump controlled by the converter and
up to 2 further pumps/fans controlled from contactors or motor starters. The contactors or
motor starter are controlled by digital outputs from the converter.
The diagram below shows a typical pumping system.
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Setting
This parameter sets the value for the increment step at the end of the nega-
tive signal period.
Range: 0.000 to 1.000 (factory default: 0.000)
This parameter sets the relative widths of the rising and falling pulses.
Range: 0 to 100 (factory default: 50)
Commissioning via the built-in BOP
5.6 Function commissioning
127