Electrical installation

Supply voltage connection

Supply voltage connection
An external 24 V supply voltage to X5:24E/GE is necessary for supplying the control electronics.
If the control electronics are supplied independently of the AC grid of the inverter, the inverter can also be
configured when the AC grid is turned off. Communication via existing networks also remains available.
DANGER!
Loss of the safe isolation
Safe isolation of the control card from the mains potential is deactivated when the motor and motor holding
brake are connected via a system cable AND X5 and X107 are supplied by a common power supply unit. This
also applies when using a SELV/PELV power supply unit.
Possible consequences: Electric shock in the event of a fault.
▶ Supply X107 and X5 by separate SELV/PELV power supply units if the motor and motor holding brake are
connected via a system cable.
24-V input
X5: 24E / GE
Use
Input voltage DC
Typical
Area
Input power
Typical
Max.
Input current
Max.
Peak
Capacity to be charged
Polarity reversal protection
Suppression of voltage pulses
Power supply unit
Max. current
152
Input for mains-independent DC supply of
the control electronics (incl. communication)
V
24
V
19.2 ... 28.8
W
20
W
45
A
1.2
A
2
µF
5500
When polarity is reversed: No function and
no irreparable damage.
Suppressor diode 30 V, bidirectional
SELV/PELV
A
12.0
IEC 61131-2
Depending on the use and state of inputs and
outputs.
For 50 ms when switching on
Externally to create a mains-independent DC
supply.
While looping-through.