Start Control Source
P100
Standard Reference
P101
Source
Lenze SMVector 13554876 EDBSV01 EN v21.0
Possible Settings
Default Selection
0
0 Local Keypad
1 Terminal Strip
2 Remote Keypad Only
3 Network Only
4 Terminal Strip or Local Keypad
5 Terminal Strip or Remote Keypad
6 CTRL button select
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters are
reset back to defaults (see P199)
NOTE
• P100 = 4, 5: To switch between control sources, one of the TB-13 inputs (P121...P124)
must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4, 6: Network can take control if P121...P124 = 9 and the corresponding
TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in JOG mode.
• TB-1 is an active STOP input if P100 is set to a value other than 0.
• An
fault will occur if the Assertion Level switch (ALsw) position does not match
F.AL
the P120 setting and P100 is set to a value other than 0.
0
0 Keypad (Local or Remote)
1 0-10 VDC
2 4-20 mA
3 Preset #1 (P131)
4 Preset #2 (P132)
5 Preset #3 (P133)
6 Network
7 Preset Sequence Segment #1 (P710) Selections 7, 8 & 9 are not valid for PID setpoint
8 Preset Sequence Segment #2 (P715)
9 Preset Sequence Segment #3 (P720)
Commissioning
Use RUN button on front of drive to start
Use start/stop circuit wired into the terminal strip.
Refer to section 3.2.3
Use RUN button on optional Remote Keypad to start
• Start command must come from network
(Modbus, CANopen, etc)
• SMV models <15HP (11kW) require optional
communication module (refer to the network
module documentation).
• Must also set one of the TB-13 inputs to 9
(Network Enable); see P121...P124
Allows start control to be switched between
terminal strip and local keypad using one of the
TB-13 inputs. See note below.
Allows start control to be switched between
terminal strip and optional remote keypad using
one of the TB-13 inputs. See Note below
Allows start control to be switched between
terminal strip and local keypad using the CTRL
button.
NOTE: P100 Selection 6 is applicable to SMV 15HP
(11kW) and higher models only.
Selects the default speed or torque reference
when no Auto Reference is selected using the
TB-13 inputs.
or torque reference.
IMPORTANT
27