I/O Modules
Output Process Image
Offset
0
1
2
3
4
5
*)
Cyclic process image (Mailbox disabled)
**)
Mailbox process image (Mailbox activated)

17.2.5.10 RTC Module

750-640
The RTC Module has a total of 6 bytes of user data in both the Input and Output
Process Image (4 bytes of module data and 1 byte of control/status and 1 byte ID
for command). The following table illustrates the Input and Output Process
Image, which have 3 words mapped into each image. Word alignment is applied.

Table 106: RTC Module 750-640

Input and Output Process Image
Offset
0
1
2

17.2.5.11 DALI/DSI Master Module

750-641
The DALI/DSI Master module has a total of 6 bytes of user data in both the Input
and Output Process Image (5 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 3
words mapped into each image. Word alignment is applied.

Table 107: DALI/DSI Master module 750-641

Input Process Image
Offset
0
1
2
Byte Destination
High Byte
reserved
D1
D3
D5
C3
C1
Byte Destination
High Byte
ID
D1
D3
Byte Destination
High Byte
D0
D2
D4
758-874/000-110 WAGO-I/O-IPC-C6
Low Byte
C0
reserved
D0
Process data*) / Mailbox**)
D2
D4
D6
Control byte C3
C2
Control byte C1 Control byte C2
Low Byte
C/S
Command byte
D0
D2
Low Byte
S
DALI Response
D1
Message 3
D3
Message 1
WAGO-I/O-SYSTEM 750
Description
Control byte C0
Process data*) /
reserved**)
Description
Control/status
byte
Data bytes
Description
Status byte
DALI Address
Message 2
Manual
Version 2.3.0