6.2

Accessories Required for Installation

To install the I/O-IPC, you will need
perforated or non-perforated mounting rails according to EN 60715 and
a 750-600 End Module.
6.3

Acceptable Mounting Directions for the I/O-IPC

The I/O-IPC can be mounted either horizontally or vertically on a mounting rail.
For vertical installation, appropriate measures shall be taken, such as using a
safeguard to prevent sliding down (B) so that the I/O-IPC does not fall down due
to vibrations and shock loads.
Heat dissipation
In order to achieve good heat dissipation for the I/O-IPC, we recommend
installing the device in mounting direction A 1 (Figure 10) on a mounting rail that
has a heat dissipating connection to the fastening site.
Pos: 36.5 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x ohne FB - Bild 1 @ 10\mod_1313398286152_21.doc @ 76862 @ @ 1
A 1
A 2

Figure 12: Mounting directions for the I/O-IPC; recommended mounting direction (A 1)

Pos: 36.6 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 2.3.0
Horizontal
Installing and Removing the I/O-IPC
B
39
Vertical
B