214

Appendix

Pos: 64 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Anhang - Überschrift 1 @ 4\mod_1239874070437_21.doc @ 30560 @ 1 @ 1
18
Appendix
Pos: 65 /Serie 758 (Funk, IPC und PFC)/Anhang/Anhang 758-87x WagoConfigToolLIB_lib @ 12\mod_1338539824410_21.doc @ 95800 @ 23 @ 1
18.1

WAGOConfigToolLIB.lib

With the function block of the CoDeSys "WAGOConfigToolLIB.lib" library,,
configure and parameterize the I/O-IPC like with the WBM and "IPC
Configuration Tool". You need the calls from the next Section. These have no
effect on the run time of the tasks because the functions are called asynchronsly.
bEnable
stCallString

Figure 85: Graphical representation of the "ConfigTool" function block

Table 116: "ConfigTool" function block

Parameter
Input
Output
Output
configToolFB
Name
Data Type
bEnable
BOOL
stCallString
STRING
(150)
bDone
BOOL
bBusy
BOOL
stResultString
STRING
(80)
iFbResult
INT
iConfigToolResult INT
stConfigToolError
STRING
String
(150)

758-874/000-110 WAGO-I/O-IPC-C6

bDone
bBusy
stResultString
iFbResult
iConfigToolResult
stConfigToolErrorString
Description
The function block starts processing when the
input registers an ascending edge.
Enter a call like in the Linux consol. An
overview of the calls is available in section
"Calls for the WAGOConfigToolLIB.lib
Library" .
Indicates whether the function block is executed
fully or after canceled after reporting an error
code.
The function block processes a call.
Return value displayed on the Linux console.
The return values have the following meaning:
0: No error
1: Invalid input parameter, e.g. an
empty string at stCallString
2: Error at implementation of the
function block
3: Unknown Configtool
4: The Configtool result string is too large
for the function block return parameter
stResultString
The value corresponds directly to the Configtool
result parameter.
This parameter displays the error description if
the call "wConfigToolResult" returns a value
≠ 0.
WAGO-I/O-SYSTEM 750