36
Description of I/O-IPC Interfaces
Boot process
During the boot process, attached devices are not permitted to send data to the
RS-232 interface because the firmware will not start otherwise. However, if this
cannot be excluded, comment the "serial" parameter out in the menu.lst file
(/boot/grub/menu.lst):
01 #serial --unit=0 --speed=115200
02 terminal --timeout=2 console
The boot loader then does not respond to the data input on the RS-232 interface.
5.6

DVI-I Interface (X7)

The DVI-I interface transmits analog and digital signals and is suitable for
connecting to digital monitors.
This interface also transmits analog image signals, so that it is possible to connect
CRT-VGA monitors while using a DVI-to-VGA adapter.
Open interface!
If this interface is not needed, it shall be closed by the protective cap provided
with delivery in order to prevent any possible damages caused by electrostatic
discharge.
WAGO-I/O-SYSTEM 750