WAGO -I/O-IPC-C6 Manual page 231

Wago-i/o-system 750
Hide thumbs Also See for WAGO-I/O-IPC-C6:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
758-874/000-110 WAGO-I/O-IPC-C6
Table 130: Description of the configuration scripts for "MODBUS"
Parameter
Baudrate
Databit
Parity
Stop Bits
Flow Control
Manual
Version 2.3.0
Status Call
get_rts3scfg_value
read
MODBUS_RTU Baud
change_rts_config
write
area=MODBUS_RTU
Baud=<value>
get_rts3scfg_value
read
MODBUS_RTU
Data_Bits
get_rts3scfg_value
read
MODBUS_RTU Parity
hange_rts_config
write
area=MODBUS_RTU
Parity=<value>
get_rts3scfg_value
read
MODBUS_RTU
Stop_Bits
change_rts_config
write
area=MODBUS_RTU
Stop_Bits=<value>
get_rts3scfg_value
read
MODBUS_RTU
Flow_control
Appendix
Output/Input
Baud rate for
MODBUS/RTU
Change the baud rate for
MODBUS/RTU. Entries for
<value> are:
2400
4800
9600
19200
38400
57600
115200
Data bit number for
MODBUS/RTU
Parity value for
MODBUS/RTU
Change the parity for
MODBUS/RTU. Entries for
<value> are:
None
Odd
Even
Stop bits for
MODBUS/RTU
Set the number of stop bits
for MODBUS/RTU. Entries
for <value> are:
1
2
Flow control value for
MODBUS/RTU
231
Validity
immediate

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents