Table 131: Description of the configuration scripts for " General SNMP information parameters "
Parameter
Add new v3-
User
Delete v3-User
Pos: 66 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 2.3.0
Status Call
config_snmp
v3-edit=add
v3-auth-name=<value1>
v3-auth-type=<value2>
write
v3-auth-key=<value3>
v3-privacy=<value4>
v3-privacy-key=<value5>
v3-notification-
receiver=<value6>
config_snmp
write
v3-edit=delete
v3-auth-name=<value>
Appendix
Output/Input
Creating a new v3 user.
v3-auth-name: user name,
string without blank
characters, maximum 32
characters. The user name
may not have been
previously assigned.
Parameters:
User name (<value1> =
string)
Encryption type: (<value2>
= none, MD5, or SHA).
Key string for
authentication, (<value3> =
string with min. 8 and max.
32 characters).
Privacy encryption type
(<value4> = none, DES, or
AES).
Privacy key string
(<value5> = string, min. 8
and max. 32 characters),
can be empty, in which case
the authentication key is
used. The
IP address of a trap receiver
is transmitted as the
notification receiver
(<value6> =
number.number.number.
number). If no v3 traps are
to be sent, this entry is
omitted.
Deleting a v3 user that has
been set up.
Because the doubled
allocation of the same user
name is prevented when
creating a user, the name is
sufficient to uniquely
identify a data set (<value>
= string).