5.3.6 Restoring Default Settings

RISK OF LOSING DATA
When restoring default settings, there is a risk of losing programming, motor data, localization, and monitoring records.
-
Provide a back-up by uploading data to the LCP before initialization.
Restoring the default parameter settings is done by initialization of the drive. Initialization is carried out via parameter 14-22 Opera-
tion Mode (recommended) or manually.
Initialization via parameter 14-22 Operation Mode does not reset the drive settings such as hours run, serial communication se-
lections, personal menu settings, fault log, alarm log, and other monitoring functions.
Manual initialization erases all motor programming, localization, and monitoring data, and restores factory default settings.

5.3.6.1 Recommended Initialization

Procedure
1.
Press [Main Menu] twice to access parameter.
2.
Scroll to parameter 14-22 Operation Mode and press [OK].
3.
Scroll to [2] Initialisation and press [OK].
4.
Remove power to the unit and wait for the display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up. This may take slightly longer than normal.
6.
Alarm 80, Drive initialised is shown.
7.
Press [Reset] to return to operating mode.

5.3.6.2 Manual Initialization

Procedure
1.
Remove power to the unit and wait for the display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at the same time while applying power to the unit (approximately 5 s or until
a click is heard and the fan starts).
Factory default parameter settings are restored during start-up. This might take slightly longer than normal.
Manual initialization resets parameter settings except for the settings in:
Parameter 15-00 Operating Hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.

5.4 Basic Operational Programming

Drives require basic operational programming before running for best performance. Basic operational programming requires enter-
ing motor nameplate data for the motor being operated and the minimum and maximum motor speeds. Enter the data in accord-
ance with the following procedure. See
with power ON, but before operating the drive.
1.
Press [Quick Menu] on the LCP.
2.
Use the navigation keys to scroll to parameter group Q2 Quick Setup and press [OK].
38 | Danfoss A/S © | 2020.07
N O T I C E
5.3.2 LCP Layout
for detailed instructions on entering data through the LCP. Enter the data
Commissioning
AQ267036816112EN-000101 / 130R0208

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT Decentral Drive FCD 302 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents