170 Parameters
No.
Name/Value
12.30
AI2 scaled at AI2
max
-32768.000...
32767.000
12.101 AI1 percent value
0.00...100.00%
12.102 AI2 percent value
0.00...100.00%
13

13 Standard AO

13.02
AO force selection
Bit
Value
0
1 = Force AO1 to value of parameter
1
1 = Force AO2 to value of parameter
2...15
Reserved
0000h...FFFFh
13.11
AO1 actual value
0.000...22.000 mA /
0.000...11.000 V
13.12
AO1 source
Zero
Motor speed used
Reserved
Output frequency
Motor current
Motor current % of
motor nominal
Motor torque
DC voltage
Output power
Reserved
Speed ref ramp in
Speed ref ramp out
Speed ref used
Reserved
Description
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
See the drawing at parameter of
Real value corresponding to maximum AI2 value.
Value of analog input AI1 in percent of AI1 scaling
max
-
12.17 AI1
min).
AI1 value
Value of analog input AI2 in percent of AI2 scaling
max
-
12.27 AI2
min).
AI2 value
Configuration of standard analog outputs.
The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
13.02
and 13.11).
Forced values selector for analog outputs AO1 and AO2.
Displays the value of AO1 in mA or V.
This parameter is read-only.
Value of AO1.
Selects a signal to be connected to analog output AO1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 147).
01.08 Motor current % of motor nom
01.10 Motor torque
(page 147).
01.11 DC voltage
(page 147).
01.14 Output power
(page 148).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
12.28 AI2
12.29 AI2 scaled at AI2
13.13 AO1 forced
value. (0 = Normal mode)
13.23 AO2 forced
value. (0 = Normal mode)
(page 147).
(page 147).
(page 147).
(page 212).
(page 213).
(page 217).
Def/FbEq16
50.000
max.
min.
1 = 1
(12.18 AI1
-
100 = 1%
(12.28 AI2
-
100 = 1%
0000h
1 = 1
-
1 = 1 mA
Output
frequency
0
1
2
3
4
5
6
7
8
9
10
11
12
13