ABB ACS580 Firmware Manual page 169

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
11.39
Freq in 1 scaled
value
-32768.000...
32767.000
11.42
Freq in 1 min
0 ... 16000 Hz
11.43
Freq in 1 max
0 ... 16000 Hz
11.44
Freq in 1 at scaled
min
-32768.000...
32767.000
11.45
Freq in 1 at scaled
max
-32768.000...
32767.000
Description
Displays the value of frequency input 1 (via DI5 or DI6 when it
is used as a frequency input) after scaling. See parameter
11.42 Freq in 1
min.
This parameter is read-only.
Scaled value of frequency input 1 (DI5 or DI6).
Defines the minimum for the frequency actually arriving at
frequency input 1 (DI5 or DI6 when it is used as a frequency
input).
The incoming frequency signal
is scaled into an internal signal
by parameters
11.42...11.45
11.39
11.45
11.44
11.42
Minimum frequency of frequency input 1 (DI5 or DI6).
Defines the maximum for the frequency actually arriving at
frequency input 1 (DI5 or DI6 when it is used as a frequency
input). See parameter
11.42 Freq in 1
Maximum frequency for frequency input 1 (DI5 or DI6).
Defines the value that is required to correspond internally to
the minimum input frequency defined by parameter
Freq in 1
min. See diagram at parameter
Value corresponding to minimum of frequency input 1.
Defines the value that is required to correspond internally to
the maximum input frequency defined by parameter
Freq in 1
max. See diagram at parameter
Value corresponding to maximum of frequency input 1.
(11.38 Freq in 1 actual
(11.39 Freq in 1 scaled
as follows:
f
(11.38)
in
11.43
min.v
11.42
11.42 Freq in 1
11.43
11.42 Freq in 1
Parameters 165
Def/FbEq16
-
1 = 1
0 Hz
value)
value)
1 = 1 Hz
16000 Hz
1 = 1 Hz
0.000
min.
1 = 1
1500.000
min.
1 = 1

Hide quick links: