ABB ACS580 Firmware Manual page 271

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
PTC DI6
Reserved
Direct temperature
KTY83 analog I/O
Description
Pt100 sensor connected to a standard analog input selected
by parameter
35.24 Temperature 2 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
PTC sensor is connected to DI6.
Note: With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter
35.22 Temperature 2 fault limit
temperature) is shown.
The temperature is taken from the source selected by
parameter
35.24 Temperature 2 AI
source is assumed to be degrees Celsius.
KTY83 sensor connected to the analog input selected by
parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
Not for ASCL2 and ASCL4 firmware. Will be available for
ASCD2 and ASCD4 firmware later.
and an analog
to
V
(volt).
AO, set the source
Temp sensor 2
I/O, but with two sensors
I/O, but with three sensors
(excessive
source. The value of the
and an analog
to
V
(volt).
AO, set the source
Temp sensor 2