232 Parameters
No.
Name/Value
28.24
Constant frequency
sel3
28.26
Constant frequency
1
-500.00...500.00
Hz
28.27
Constant frequency
2
-500.00...500.00
Hz
28.28
Constant frequency
3
-500.00...500.00
Hz
28.29
Constant frequency
4
-500.00...500.00
Hz
28.30
Constant frequency
5
-500.00...500.00
Hz
28.31
Constant frequency
6
-500.00...500.00
Hz
28.32
Constant frequency
7
-500.00...500.00
Hz
28.41
Frequency ref safe
-500.00...500.00
Hz
Description
When bit 0 of parameter
0 (Separate), selects a source that activates constant
frequency 3.
When bit 0 of parameter
1 (Packed), this parameter and parameters
frequency sel1
and
28.23 Constant frequency sel2
three sources that are used to activate constant frequencies.
See table at parameter
For the selections, see parameter
sel1.
Defines constant frequency 1 (the frequency the motor will
turn when constant frequency 1 is selected).
Constant frequency 1.
Defines constant frequency 2.
Constant frequency 2.
Defines constant frequency 3.
Constant frequency 3.
Defines constant frequency 4.
Constant frequency 4.
Defines constant frequency 5.
Constant frequency 5.
Defines constant frequency 6.
Constant frequency 6.
Defines constant frequency 7.
Constant frequency 7.
Defines a safe frequency reference value that is used with
supervision functions such as
•
12.03 AI supervision function
•
49.05 Communication loss action
• 50.02 FBA A comm loss func.
Safe frequency reference.
28.21 Constant frequency function
28.21 Constant frequency function
28.22 Constant
28.22 Constant frequency sel1.
28.22 Constant frequency
Def/FbEq16
is
Not selected
is
select
5.00 Hz
See par.
46.02
10.00 Hz
See par.
46.02
15.00 Hz
See par.
46.02
20.00 Hz
See par.
46.02
25.00 Hz
See par.
46.02
40.00 Hz
See par.
46.02
50.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02