382 Fault tracing
Code
Warning / Aux. code
(hex)
A4A9
Cooling
A4B0
Excess temperature
A4B1
Excess temperature
difference
A4F6
IGBT temperature
A580
PU communication
A582
Auxiliary fan missing
A5A0
Safe torque off
Programmable warning:
31.22 STO indication
run/stop
A5EA
Measurement circuit
temperature
A5EB
PU board powerfail
Cause
Drive module temperature is
excessive.
Power unit module
temperature is excessive.
High temperature difference
between the IGBTs of different
phases.
Drive IGBT temperature is
excessive.
Communication errors
detected between the drive
control unit and the power unit.
An auxiliary cooling fan
(connected to the fan
connectors on the control
board) is stuck or
disconnected.
0001 Auxiliary fan 1 missing.
0002 Auxiliary fan 2 missing.
Safe torque off function is
active, ie safety circuit signal(s)
connected to connector STO is
lost.
Problem with internal
temperature measurement of
the drive.
Power unit power supply
failure.
What to do
Check ambient temperature. If it exceeds
40 °C/104 °F (IP21 frames R4
it exceeds 50 °C /122 °F (IP21 frames
...
R0
R9), ensure that load current does
not exceed derated load capacity of
drive. For all P55 frames, check the
derating temperatures. See chapter
Technical data, section Derating in the
Hardware manual of the drive.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check the motor cabling.
Check cooling of drive module(s).
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check the connections between the drive
control unit and the power unit.
Check the value of parameter
Control board
supply.
Check the auxiliary code.
Check auxiliary fan(s) and connection(s).
Replace faulty fan.
Make sure the front cover of the drive is
in place and tightened. If the
commissioning of the drive requires that
the cover is off, this warning will be
generated even if the corresponding fault
is defeated. See fault
5081 Auxiliary fan
broken
(page 392).
Check safety circuit connections. For
more information, chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication run/stop
(page 245).
Check the value of parameter
Control board
supply.
Contact your local ABB representative.